The SINAUT Configuration Tool
6.9 Downloading
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
239
6.9
Downloading
6.9.1
Downloading data blocks to the CPU
To download data blocks to the CPU module, you use the STEP 7 SIMATIC Manager
standard tool. This allows you to copy blocks using drag-and-drop or a menu either in an
online window (configured online access) or in the window with the accessible nodes (non-
configured online access).
Note
When you download blocks to the automation system by dragging and dropping, you
yourself are responsible for ensuring that the blocks are copied to the correct online object
(in other words, the object with the correct MPI address). The STEP 7 tool does not check
this.
For more detailed information on these activities, refer to the online help of the SIMATIC
Manager.
6.9.2
Downloading system data blocks to the TIM
You should only download system data blocks (SDBs) to the TIM in the SIMATIC Manager
or in the SINAUT diagnostics and service tool.
Note
When downloading system data blocks in
hardware configuration
, make sure that
no
connection SDBs (SDB7xx) are downloaded. If SDBs of this type need to be downloaded to
the TIM module, you must use the SIMATIC Manager or the SINAUT diagnostics and
service tool.
SDBs can also be downloaded in
network configuration
. Creating SDBs during network
configuration is a different procedure from that in the SIMATIC Manager and hardware
configuration and is not suitable for the TIM module. Copying SDBs to TIM modules should
therefore only be done in the SIMATIC Manager or SINAUT diagnostics and service tool.
In the SIMATIC Manager, all SDBs of a module are indicated by a symbol with the name
System data
. This means that you can only ever manipulate all SDBs of a module as a
single unit. Otherwise, the same applies as for data blocks.
In the hardware configuration, it is possible to download the SDBs of individual modules or
entire stations.
In both cases, the function is followed by a dialog in which you are asked whether you want
to restart the TIM module. This dialog must be exited with
Yes
to restart the TIM and activate
the new SDBs.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...