![Siemens SIMATIC TIM 3V-IE DNP3 Скачать руководство пользователя страница 300](http://html.mh-extra.com/html/siemens/simatic-tim-3v-ie-dnp3/simatic-tim-3v-ie-dnp3_system-manual_1265391300.webp)
Technical specifications
8.1 Technical specifications of the TIM 3V-IE DNP3
TIM DNP3
300
System Manual, 12/2015, C79000-G8976-C253-04
Technical specifications of the TIM 3V-IE DNP3
Permitted ambient conditions
Ambient temperature
During operation with the rack in-
stalled horizontally
0 ℃ to +60 ℃
During operation with the rack in-
stalled vertically
0 ℃ to +40 ℃
During storage
-
40 ℃ to +70 ℃
During transportation
-
40 ℃ to
+70 ℃
Relative humidity
During operation
≤ 95 % at 25 °C, no condensation
Operating altitude
During operation
≤
2,000 m above sea level at max. 60 °C
ambient temperature
Contaminant concentration
Acc. to ISA-S71.04 severity level G1, G2, G3
Design, dimensions and weight
Module format
Compact module for S7-300, single width
Degree of protection
IP20
Weight
250 g
Dimensions (W x H x D)
40 x 125 x 120 mm
Installation options
•
Installation on a DIN rail
•
Installation on an S7-300 standard rail
•
Wall mounting
•
Mounting in a 19" rack
•
Switch panel
Product functions *
Configuration
Software for PG
SINAUT configuration software for PG
Storage of TIM configuration data
•
on internal TIM flash memory
•
on MMC of the S7-300-CPU
TIM can be operated in the role
•
Station
•
Node station
•
Master station
•
yes
•
yes
•
yes
No. of TIM 3V-IE DNP3 modules per
S7-300
1
Local communication
Via backplane bus with the S7-300
CPU
possible using TD7onTIM
Via backplane bus with other TIMs in
the rack
Not possible
Via MPI interface of the S7-300 CPU
with other CPUs, TIMs, and/or PCs
Not possible
Work memory required on the S7
CPU
TD7onTIM software
Best case, 0 bytes
Data memory on the TIM
Battery backed
no
Transmission protocol RS-232
Selectable protocols
DNP3
Asynchronous character format
(DNP3)
10 bits
Hamming distance d (DNP3)
2
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...