The input address
Data written from TD7onTIM to the MODBUS slaves is read from the input address area of
the CPU. Only the specified address areas can be read by TD7onTIM. Data from other
areas, for example analog values acquired over peripheral input words (PIW) must be
mapped to the bit memory or data block area by the user program.
Name:
S7 CPU input address
Memory area: The following options are available for the source address:
•
DB: Data block
•
Memory bit: Memory bit area
•
Input: Process input image (PII)
Data type:
By specifying the data type, you specify the data type with which the data is
transferred from the S7 CPU to the MODBUS slaves. The drop-down list
offers the following data types for the three memory areas:
BOOL, BYTE, CHAR, WORD, DWORD, INT, DINT, REAL
Number:
Number of double words included in the array (maximum 100).
DB No.:
Specifies the DB number in the CPU if the data block memory area (DB) was
selected
Address [Byte]: Input field for the byte number in the selected memory area. For data types
involving more than one byte (WORD, DWORD), the least significant byte
number must be entered as in STEP 7.
MODBUS output
Here, the register address on the MODBUS slave to which the data will be written is
specified.
Name:
MODBUS output
Register ad-
dress:
Specifies the register address.
You will find the permitted address ranges in the documentation of your MODBUS
slave.
Range of val-
ues:
0...65535
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...