Configuration in STEP 7
5.9 Configuring time-of-day synchronization
TIM DNP3
136
System Manual, 12/2015, C79000-G8976-C253-04
The TIM in the S7-300 makes the time of day available to its local CPU in the I/O addresses.
The CPU user program can then read and evaluate the time there.
The I/O addresses of the CPU that makes the date and time information available to the TIM
are set in the properties dialog of the TIM, "Addresses" tab; refer to the section "Addresses"
tab (Page 116).
The time information of a time-synchronized TIM module with TD7onTIM is stored in 8 bytes
of the peripheral inputs. The time information has an offset of 8 bytes from the start value of
the inputs. The following table shows the assignment of the 8 bytes of time information.
Time-of-day format
Table 5- 1
Format of the time information in the inputs of the I/O addresses of the TIM
Byte No.
Offset
[bytes]
Meaning
High nibble
Low nibble
Value
Range of val-
ues (decimal)
Value
Range of val-
ues (decimal)
1
+8
Year
tens
0...9
ones
0...9
2
+9
Month
tens
0...9
ones
0...9
3
+10
Tag
tens
0...9
ones
0...9
4
+11
Hour
tens
0...9
ones
0...9
5
+12
Minute
tens
0...9
ones
0...9
6
+13
Second
tens
0...9
ones
0...9
7
+14
Millisecond
hundreds
0...9
tens
0...9
8
+15
Millisecond
ones
0...9
Status
bit coded
Meaning of the entries in the table:
●
Offset: Offset to the base value of the peripheral inputs in bytes
●
High nibble: Bits 4-7
●
Low nibble: Bits 0-3
●
Value: Position of the relevant number
–
Year, month, day, hour, minute and second are two-digit (tens + ones)
–
Milliseconds are three-digit (hu tens + ones)
●
Status: Status of the time information
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...