The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
213
Specifying the data type specifies how the data of the S7 CPU is interpreted and transmitted
to the communications partner.
The number of required elements, in other words the size of the data field is configured in
the Number input box.
The configured number of values specifies how many DNP3 indexes are occupied
consecutively by the object starting with the specified start index. The following assignment
between the data type used and the index used applies:
Data type
Range of values
Number of DNP3 indexes
occupied
BYTE
0 .. 255
4 ... 48
CHAR
Printable ASCII characters
4 ... 48
WORD
0 .. 65 535
2 ... 24
INT
-32 768 .. 32 767
2 ... 24
DINT
-2 147 483 648 .. 2 147 483 647
1 ... 12
DWORD
0 .. 4 294 967 295
1 ... 12
REAL
≈
-3,4 * 10
38
.. 3,4 * 10
38
1 ... 12
You will find the DNP3 object groups compatible with the individual data types in the section
Objects of TD7onTIM (Page 177).
Note
Reducing network load
By reducing the maximum size (parameter “Number”), the message length can be reduced
to the actually required length if the entire data range of the object is not required. This saves
transmission time.
Dat12D_R
Channel "DataOutput"
Channel type: Data receive
Dat12D_R allows receipt of data with a size of up to 12 double words.
The master station can send all variations of the DNP3 object group "Analog output". If the
transferred analog value is outside the range of validity of the configured data type, this
value is not transferred to the S7 CPU. A negative acknowledgement is sent to the master
station.
Output address
Setting the data type specifies how the data of the communications partner will be
interpreted and in the case of the station transferred to the S7 CPU.
The number of required elements, in other words the size of the data field is configured in
the Number input box.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...