![Siemens SIMATIC TIM 3V-IE DNP3 Скачать руководство пользователя страница 277](http://html.mh-extra.com/html/siemens/simatic-tim-3v-ie-dnp3/simatic-tim-3v-ie-dnp3_system-manual_1265391277.webp)
Diagnostics and upkeep
7.3 SINAUT diagnostics and service tool
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
277
Operator activities
Note
Make sure that you select the correct TIM module in your project. The station and module
name must match and the configured module must be of the same type as the module to
which you are downloading.
If this is not the case, a dialog will inform you of this at regular intervals during the update.
The display of this message interrupts the update until the dialog is acknowledged by
clicking on
OK
.
1.
Select the relevant TIM in the
SINAUT subscriber list
of the open project.
2.
Start the function by selecting the
SINAUT / Firmware Update
menu. The
Firmware
Update
dialog opens.
3.
Click on the
Update details
button if you require a detailed information on the firmware
update. The
Update details
dialog opens.
4.
Click on the
Update
button in the
Firmware Update
dialog to start the firmware update.
The following dialog
Loading
informs you of the current progress of the update.
5.
On completion of the firmware update, a dialog appears with a message to this effect.
Confirm the message with
OK
.
Update details
dialog
The
Update details
dialog that can be opened from the
Firmware Update
dialog displays
detailed information on the firmware update. The function and version of each firmware
component on the TIM module and on the PG is shown and you can see whether the
relevant component is copied, replaced, ignored, or deleted during the firmware update.
The various actions have the following significance:
●
copy: The file is copied from the PG to the TIM module.
●
replace: The file on the TIM module is replaced by the file on the PG.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...