![Siemens SIMATIC TIM 3V-IE DNP3 Скачать руководство пользователя страница 85](http://html.mh-extra.com/html/siemens/simatic-tim-3v-ie-dnp3/simatic-tim-3v-ie-dnp3_system-manual_1265391085.webp)
Configuration in STEP 7
5.4 Creating stations and networks in network configuration
TIM DNP3
System Manual, 12/2015, C79000-G8976-C253-04
85
5.4
Creating stations and networks in network configuration
The STEP 7
NetPro
tool is used for graphic configuration of network topologies. During
network configuration, networks and stations are added to a new project, given parameter
settings, and interconnected. The various network types and stations are available in the
network and station catalog. The basic functions and possible settings are described in the
STEP 7 documentation.
5.4.1
Creating non-STEP 7 stations
Creating non-STEP 7 stations
The term "Station" is used in STEP 7 as general term for a station that appears in hardware
configuration.
STEP 7 supports the configuration of different types of non-STEP 7 stations. This can be a
DNP3 master station (e.g. PCS 7 control center). As with the STEP 7 stations, they are
created by double-clicking on the icon in the station catalog or by dragging them to the
project window. The following objects must be selected for these subscribers:
●
For a PC-based DNP3 master station: "Other station"
This third-party station is simply used as a placeholder for the network configuration. A
hardware configuration for a third-party station of the type "DNP3 master station" is not
possible since its content is unknown to STEP 7.
●
Modbus slave
To connect a Modbus slave to the serial interface of the DNP3 TIM, no station needs to
be created in STEP 7.
To attach created stations to the networks of the project, module capable of communication
are first configured for the STEP 7 stations in HW Config so that the required interfaces can
then be configured.
With third-party stations, the interfaces can be created immediately.
Creating the interfaces for non-STEP 7 stations
●
DNP3 master station
A DNP3 master station (Other station) can be configured with any number of DNP3
dedicated lines and Industrial Ethernet. To do this call up the Properties dialog using the
shortcut menu.
5.5
Configuring stations in STEP 7 / HW Config
The hardware configuration program HW Config is used to install hardware components in
stations. The HW Config program is opened by double-clicking on one of the station icons
configured in the network configuration.
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...