The SINAUT Configuration Tool
6.6 TD7onTIM
TIM DNP3
212
System Manual, 12/2015, C79000-G8976-C253-04
Mean04W_S
Channel "MeanValueInput_x"
Channel type: Mean value send
Mean04W_S allows sending of up to 4 analog mean values. The data object is divided into 4
channels to each of which an analog value is assigned. Values in the range from 0 to 65535
are transferred.
The object occupies 4 indexes (1 index per activated channel).
Mean04W_R
Channel "MeanValueOutput_x"
Channel type: Mean value receive
Mean04W_R allows receipt of up to 4 analog mean values. The data object is divided into 4
channels to each of which an analog value is assigned.
The object occupies 4 indexes (1 index per activated channel).
As the data destination, an S7 word variable is specified for each active channel. When
receiving, values in the range from 0 to 65535 are accepted.
If values outside the range of validity are received, in the case of a station, the value is not
transferred to the S7 CPU. The DNP3 master station receives a negative acknowledgment
for such a command. For other ranges of validity, the data object "Dat12D_R" is available.
Note that with a write operation of the DNP3 master station, all active channels of the data
object are transferred to the assigned S7 CPU by TD7onTIM, even if the DNP3 master
station only sends 1 channel.
Dat12D_S
Channel "DataInput"
Channel type: Data send
Dat12D_S allows the sending of data of a size up to 12 double words in 1 channel.
Input address
Image 6-22 "Input address" box in the dialog of the "DataInput" channel
Содержание SIMATIC TIM 3V-IE DNP3
Страница 12: ...Table of contents TIM DNP3 12 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 298: ...Diagnostics and upkeep 7 3 SINAUT diagnostics and service tool TIM DNP3 298 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 306: ...Technical specifications 8 3 Current consumption and power loss TIM DNP3 306 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 311: ...Approvals TIM DNP3 System Manual 12 2015 C79000 G8976 C253 04 311 ...
Страница 312: ......
Страница 332: ...Accessories A 5 LTOP overvoltage protection modules TIM DNP3 332 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 340: ...PG routing via WAN B 3 Preparations for PG routing TIM DNP3 340 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 350: ...Glossary TIM DNP3 350 System Manual 12 2015 C79000 G8976 C253 04 ...
Страница 354: ...Index TIM DNP3 354 System Manual 12 2015 C79000 G8976 C253 04 ...