Technical specifications
Article number
Rack UR5213
6DD1682-0CH2
General data
Safety
EN 61131-2
Degree of protection
IP 20
Protection class
Protection class 1 with PE/ground conductor
Storage temperatures
-40 °C to +70 °C
Operating temperatures
0 °C to +60 °C
Relative air humidity
5 % to 95 %, no condensation
Atmospheric pressure
Operation: 1080 hPa to 795 hPa
Storage: 1080 hPa to 660 hPa
Power input
Input voltage
•
Rated value
•
Permissible range
120/230 V AC
220 V DC
85 V AC to 264 V AC
198 V DC to 253 V DC (extended range input)
Rated input current
•
At 120 V AC
•
At 230 V AC
•
At 220 V DC
4.45 A
2.3 A
2.38 A
Max. inrush current
< 40 A
Line frequency
•
Rated value
•
Permissible range
50/60 Hz
47-63 Hz
Power factor
EN 61000-3-2
Overvoltage category
II
Pollution degree
2
Power failure backup
min. 20 ms