Execution Times for STL Instructions
Table E-1 lists the basic execution times of the STL instructions for the CPU 210. The
calculation of the basic execution time for an STL instruction shows the time required for
executing the logic, or function, of the instruction when power flow is present (where the
top-of-stack value is ON or 1).
For some instructions, the execution of that function is conditional upon the presence of
power flow: the CPU performs the function only when power flow is present to the instruction
(when the top-of-stack value is ON or 1).
The overhead for the CPU 210 is 140
s per scan. There is also an additional overhead that
is associated with the system clock: add 60
s for every 1 ms counted by the system clock.
Table E-1
Execution Times for the STL Instructions (in
µ
s)
Instruction
Description
On (
µ
s)
Off (
µ
s)
=
Output
valid for Q, M
120
120
A
And
valid for I, M, SM
110
110
ALD
And Load
60
60
AN
And Not
valid for I, M, SM
80
80
AW < =
And Word if less than or equal
300
300
AW=
And Word if equal
300
300
AW > =
And Word if greater than or equal
300
300
CTUD
Up/Down Counter
110
100
DECW
Decrement Word
140
70
DISI
Disable Interrupts
60
60
ED
Edge Down (Negative Transition)
120
120
ENI
Enable Interrupts
60
60
EU
Edge Up (Positive Transition)
110
110
INCW
Increment Word
140
70
INT
Interrupt Routine
Add 110
µ
s if the interrupt routine uses any of the
following instructions:
S
MOVW
S
LDW<=, LDW>=, LDW=
S
OW<=, ,OW>=, OW=
S
AW<=, AW>=, AW=
30
Not applicable
JMP
Jump to Label
70
70
LBL
Label
0
0
E
Содержание Simatic S7-200 CPU 210
Страница 10: ...x S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Contents ...
Страница 68: ...3 28 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Getting Started with a Sample Program ...
Страница 116: ...A 16 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Data Sheets ...
Страница 126: ...F 2 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 CPU 210 Order Numbers ...
Страница 138: ...Index 12 S7 200 Programmable Controller CPU 210 C79000 G7076 C235 01 Index ...