PROFIBUS DP Master Interface IM 467/IM 467 FO
8-8
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
8.3
Connection to PROFIBUS DP
There are two ways of connecting to PROFIBUS DP:
•
Electrical connection via a bus connector
•
Optical connection using a fiber-optic cable
8.3.1
Bus Connector
Only with 6ES7467-5GJ02-0AB0.
The bus cable is connected to the IM 467 by means of this connector. (See the
detailed description in the chapter on networking in the S7-400/M7-400, Hardware
and Installation manual.)
Bus connector
PROFIBUS DP bus cable
Switch for the bus
terminating resistor
Figure 8-3
Connecting the Bus Connector to the IM 467
Maximum Cable Lengths for PROFIBUS DP
Transmission Rate in
Kbps
9.6
19.2
93.75
187.5
500
1500
3000
6000 W
12000
Max. Length of a Bus
Segment in m
1.000
1.000
1.000
1.000
400
200
100
100
100
Max. Number of Bus
Segments 1)
10
10
10
10
10
10
10
10
10
Max. Length in m
10.000 10.000 10.000 10.000 4.000
2.000
1.000
1.000
1.000
1)
Bus segments are interconnected by means of RS 485 repeaters
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......