Digital Modules
4-11
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Causes of Errors and Remedial Measures for Digital Modules
Table 4-9
Diagnostic Messages of the Digital Modules, Causes of Errors and Remedial
Measures
Diagnostic Message
Possible Error Cause
Remedy
Module malfunction
An error detected by the module
has occurred
-
Internal malfunction
The module has detected an error
within the programmable controller
-
External malfunction
The module has detected an error
outside the programmable controller
-
There is a channel
error
Indicates that only certain channels
are faulty
-
No external auxiliary
voltage
Voltage required to operate the
module is missing (load voltage,
sensor supply)
Supply missing voltage
No front connector
Jumper between connections 1 and
2 in the front connector missing
Install jumper
Parameters have not
been assigned to the
module
The module requires the information
as to whether it should work with
system default parameters or with
your parameters
Message queued after power-on until
parameter transmission by the CPU has
been completed; parameterize the
module, as required
Wrong parameters
One parameter or the combination
of parameters is not plausible
Reassign module parameter
Channel information
available
Channel error present; the module
can supply additional channel
information
-
Operating mode
STOP
Module was not parameterized and
the first module cycle has not been
completed
If after rebooting the CPU all the input
values are in the intermediate memory,
this message is reset
Internal voltage failure
Module is defective
Replace module
EPROM error
Module is defective
Replace module
Hardware interrupt lost
The module cannot send an
interrupt, since the previous
interrupt was not acknowledged;
configuration error possible
Change the interrupt handling in the CPU
(change priority for interrupt OB; shorten
interrupt program)
Parameter assignment
error
Incorrect parameters transferred to
the module (for example, impossible
input delay); the corresponding
channel is deactivated
Reassign module parameter
Short circuit to M
Overload of output
Eliminate overload
Short-circuit of output to M
Check the wiring of the outputs
Short circuit to L+
Short circuit of output to L+
Check the wiring of the outputs
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......