Digital Modules
4-35
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Status, Interrupts, Diagnostics
Status display
Green LED per
channel
Interrupts
•
Hardware interrupt
•
Diagnostic Interrupt
Parameters can be
assigned
Parameters can be
assigned
Diagnostic functions
•
Monitoring of the power
supply voltage of the
electronics
Yes
•
Load voltage monitor
Green LED per group
•
Group error display
–
For internal fault
–
For external fault
Red LED (INTF)
Red LED (EXTF)
•
Channel error display (F)
None
•
Diagnostic information can
be displayed
Yes
Monitoring for
•
Wire break
I < 1 mA
Substitute value can be applied
Yes
Sensor Power Supply Outputs
Number of outputs
2
Output voltage
•
with load
Min. L+(–2.5 V)
Output current
•
Rated value
•
Permitted range
120 mA
0 to 150 mA
Additional (redundant) supply
Possible
Short-circuit protection
Yes, electronic
Data for Selecting a Sensor
Input voltage
•
Rated value
•
For signal “1”
•
For signal “0”
24 VDC
11 V to 30 V
-30 V to 5 V
Input current
•
At signal “1”
•
At signal “0”
6 mA to 12 mA
< 6 mA
Input characteristic curve
To IEC 61131;
type 2
Connection of two-wire BEROs
•
Permitted bias current
Possible
Max. 3 mA
Time, Frequency
Internal preparation time
1)
for
•
only status recognition
–
Input delay of the
channel groups
0.05 ms/0.05 ms
max. 50
s
–
Input delay of the
channel groups
0.05 ms/0.1 ms or 0.1
ms/0.1 ms
max. 70
s
–
Input delay of the
channel groups
>= 0.5 ms
max. 180
s
•
Status recognition and
enable process interrupt
–
Input delay of the
channel groups
0.05 ms/0.05 ms
2)
max. 60
s
–
Input delay for the
channel groups
0.05 ms/0.1 ms or 0.1
ms/0.1 ms
max. 80
s
–
Input delay of the
channel groups
>= 0.5 ms
max. 190
s
Internal preparation time for
diagnostics/diagnostic interrupt
Input delay
max. 5 ms
•
Parameters can be
assigned
Yes
•
Rated value
0.1/0.5/3 ms
•
Input frequency
(with a time delay of
0.1 ms)
< 2 kHz
Values go into cycle and response times.
Sensor Circuit
Resistance circuit of the sensor
for wire break monitoring
10 to 18 k
Ω
1) The filter times are added to the overall runtime of the
selected input delay.
2) Substitute functionality; diagnostics and diagnostic
interrupt are not to be selected.
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......