Interface Modules
6-2
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
6.1
Common Features of the Interface Modules
Function
Interface modules (a send IM and a receive IM) are required if one or more
expansion units (EU) are to be connected to a central controller (CC). This
configuration is described in the Installation Manual, Chapter 4.
Configuration
Interface modules must always be used together. The send modules (send IMs)
are inserted in the CC, whilst the corresponding receive modules (receive IMs) are
plugged into the series-connected EU.
Table 6-1
Interface Modules of the S7-400
Partner
Areas of Application
IM 460-0
Send IM for local link without PS transfer; with communication bus
IM 461-0
Receive IM for local link without PS transfer; with communication bus
IM 460-1
Send IM for local link with PS transfer; without communication bus
IM 461-1
Receive IM for local link with PS transfer; without communication bus
IM 460-3
Send IM for remote link up to 102 m; with communication bus
IM 461-3
Receive IM for remote link up to 102 m; with communication bus
IM 460-4
Send IM for remote link up to 605 m; without communication bus
IM 461-4
Receive IM for remote link up to 605 m; without communication bus
Overview of the Properties of the Connections
Note the rules for connections in the section after next.
Local connection
Remote connection
Send IM
460-0
460-1
460-3
460-4
Receive IM
461-0
461-1
461-3
461-4
Max. number of connectable EMs per
chain
4
1
4
4
Max. distance
3 m
1.5 m
102.25 m
605 m
5 V transfer
No
Yes
No
No
Max. current transfer per interface
–
5 A
–
–
Communication bus transmission
Yes
No
Yes
No
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......