Power Supply Modules
3-14
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Table 3-8
INTF, DC5V, DC24V LEDs, continued
LED
INTF
Remedy
Cause of Fault
DC24V
DC5V
H
D*
D
Short circuit or overload on 5 V and
24 V
Check load on the power supply
module.
Possibly remove modules
H
D*
H/D **
Short circuit or overload on 5 V
Check load on the power supply
module. Possibly remove modules
H
H
D
If the standby switch is at the
position, illegal external supply on 5 V
Remove all modules.
Determine which module is faulty
If the standby switch is at the
I
position, short-circuit or overload on
24 V
Check load on the power supply
module.
Possibly remove modules
D
B
H
Voltage restored after short circuit or
overload on 5 V if faults occur in
operation
Press FMR momentary-contact
pushbutton:
Flashing light changes to constant light
Dynamic overload on 5 V
Check load on the power supply
module.
Possibly remove modules
D
H
B
Voltage restored after short-circuit or
overload on 24 V if faults occur in
operation
Press FMR momentary-contact
pushbutton:
Flashing light changes to constant light
Dynamic overload on 24 V
Check load on the power supply
module.
Possibly remove modules
D
B
B
Voltage restored after short circuit or
overload on 5 V and 24 V if faults occur
in operation
Press FMR momentary-contact
pushbutton:
Flashing light changes to constant light
D
B
B
Dynamic overload on 5 V and 24 V
Check load on the power supply
module.
Possibly remove modules
D = LED is dark; L = LED lights up; F = LED flashing;
* If the power supply module does not start up again after a few seconds once the
overload has been removed, remove power to the module for 5 minutes and then
switch it on again. If the module stills does not start up, you must replace it. This
applies to 6ES7407-0KA01-0AA0, release 3 and for 6ES7407-0KR00-0AA0,
release
≤
5.
** Depending on the short-circuit resistance
If either the 5 VDC or 24 VDC LEDs remains dark after switching on, the system
has not powered up.
If either of the 5 VDC or 24 VDC LEDs of the PS 407 10AR remains dark for longer
than 1 or 2 seconds after it is switched on, the power supply module will not start
up.
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......