Analog Modules
5-113
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Status, Interrupts, Diagnostics
Interrupts
•
Hardware interrupt
Parameters can be
assigned
•
Hardware interrupt when
limit has been exceeded
Parameters can be
assigned
•
Diagnostic Interrupt
Parameters can be
assigned
Diagnostic functions
•
Group error display
–
For internal fault
–
For external fault
Red LED (INTF)
Red LED (EXTF)
•
Diagnostic information
readable
Yes
Substitute value can be applied
No
Data for Selecting a Sensor
Input range (rated values)/Input
resistance
•
Voltage
"
25 mV/1 M
"
50 mV/1 M
"
80 mV/1 M
"
250 mV/1 M
"
500 mV/1 M
"
1 V/1 M
"
2.5 V/1 M
"
5 V/1 M
1 V to 5 V
1 M
"
10 V/1 M
•
Current
0 mA to 20 mA
50
"
5 mA/50
"
10 mA/50
"
20 mA/50
4 mA to 20 mA
50
•
Resistors
0 to 48
1 M
0 to 150
1 M
0 to 300
1 M
0 to 600
1 M
0 to 6000
1 M
(can be used up to
5000
)
•
Thermocouples
TC type B/1 M
TC type R/1 M
TC type S/1 M
TC type T/1 M
TC type E/1 M
TC type J/1 M
TC type K/1 M
TC type U/1 M
TC type L/1 M
TC type N/1 M
•
Resistance thermometer
Pt 100/1 M
Pt 200/1 M
Pt 500/1 M
Pt 1000/1 M
Ni 100/1 M
Ni 1000/1 M
Maximum input voltage for
voltage input
(destruction limit)
Max. 18 V continuous;
75 V for 1 ms (cycle
factor 1 : 20)
Maximum input current for
current input (destruction limit)
40 mA
Connection of the signal
sensor
•
For measuring voltage
Possible
•
For measuring current
–
As two-wire
transmitter
Possible
–
As four-wire
transmitter
Possible
•
For measuring resistance
–
With two-conductor
terminal
Possible; cable
resistance is also
measured
–
With three-conductor
terminal
Possible
–
With four-conductor
terminal
Possible
•
Load of the two-wire
transmitter
Max. 750
Characteristic linearization
Parameters can be
assigned
•
For thermocouples
Types B, R, S, T, E, J,
K, U, L, N
•
For
resistance thermometer
Pt 100, Pt 200, Pt 500,
Pt 1000, Ni 100,
Ni 1000
Temperature compensation
Yes, programmable
•
Internal temperature
compensation
No
•
External temperature
compensation with
compensating box
Possible
•
External temperature
compensation with Pt 100
Possible
•
Compensation for
definable reference
junction
temperature
Possible
Unit for temperature
measurement
Degrees Celsius
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......