Analog Modules
5-20
S7-400, M7-400 Programmable Controllers Module Specifications
A5E00069467-07
Analog Value Representation for Thermocouple Type L
Table 5-26 Analog Value Representation for Thermocouple Type L
Type L
Units
Type L
Units
Type L
Units
Type L
in
5
C
Decimal
Hexa-
decimal
Type L
in
5
F
Deci-
mal
Hexa-
deci-
mal
Type L
in K
Deci-
mal
Hexa-
decimal
Range
> 1150.0
32767
7FFF
H
> 2102.0
32767
7FFF
H
> 1423.2
32767
7FFF
H
Overflow
1150.0
:
901.0
11500
:
9010
2CEC
H
:
2332
H
2102.0
:
1653.8
21020
:
16538
521C
H
:
409A
H
1423.2
:
1174.2
14232
:
11742
3798
H
:
2DDE
H
Overrange
900.0
:
–200.0
9000
:
–2000
2328
H
:
F830
H
1652.0
:
–328.0
16520
:
–3280
4088
H
:
F330
H
1173.2
:
73.2
11732
:
732
2DD4
H
:
02DC
H
Rated range
< –200.0
< –2000
< F830
H
< –328.0
<
–3280
<F330
H
< 73.2
< 732
<02DC
H
Underflow
In the case of incorrect wiring (for example, polarity reversal or open inputs) or of a sensor error in the
negative range (for example, incorrect thermocouple type), the analog input module reports an
underflow...
...if F380
H
is violated and outputs
8000
H
...if EAC0
H
is violated and
outputs 8000
H
...if FE2C
H
is violated and
outputs 8000
H
Analog Value Representation for Thermocouple Type N
Table 5-27 Analog Value Representation for Thermocouple Type N
Type N
Units
Type N
Units
Type N
Units
Type N
in
5
C
Deci-
mal
Hexade-
cimal
Type N
in
5
F
Deci-
mal
Hexa-
deci-
mal
Type N
in K
Deci-
mal
Hexa-
deci-
mal
Range
> 1550.0
32767
7FFF
H
> 2822.0
32767
7FFF
H
> 1823.2
32767
7FFF
H
Overflow
1550.0
:
1300.1
15500
:
13001
3C8C
H
:
32C9
H
2822.0
:
2373.8
28220
:
23738
6E3C
H
:
5CBA
H
1823.2
:
1574.2
18232
:
15742
4738
H
:
3D7E
H
Overrange
1300.0
:
–270.0
13000
:
–2700
32C8
H
:
F574
H
2372.0
:
–454.0
23720
:
–4540
5CA8
H
:
EE44
H
1573.2
:
0
15732
:
0
3D74
H
:
0000
H
Rated range
< –270.0
<
–2700
< F574
H
< –454.0
<
–4540
<EE44
H
< 0
< 0
<
0000
H
Underflow
In the case of incorrect wiring (for example, polarity reversal or open inputs) or of a sensor error in the
negative range (for example, incorrect thermocouple type), the analog input module reports an
underflow...
...if F0C4
H
is violated and
outputs 8000
H
...if E5D4
H
is violated and
outputs 8000
H
...if FB70
H
is violated and
outputs 8000
H
Содержание Simatic M7-400
Страница 10: ...Preface x S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 122: ...Power Supply Modules 3 42 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 362: ...Analog Modules 5 146 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 384: ...Interface Modules 6 22 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 428: ...RS 485 Repeater 10 8 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 496: ...M7 400 Expansions 12 26 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 562: ...Interface Submodules 13 66 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 574: ...Parameter Sets for Signal Modules A 12 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 594: ...Diagnostic Data of the Signal Modules B 20 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 598: ...Spare Parts and Accessories C 4 S7 400 M7 400 Programmable Controllers Module Specifications A5E00069467 07 ...
Страница 606: ......