Diagnostics Using the User Program
10-8
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
10.2.3
Module status
The module status is part of the station diagnosis and indicates the status of the
configured modules.
Structure of the module status
The module status consists of 63 bytes.
In the module status, the status is encoded by means of two bits for each slot (see
Section 10.2.2).
The following applies to the entry in the module status:
If an underlying slave delivers its own module status in its diagnosis, this status
is copied to the appropriate location.
If an underlying slave delivers a module diagnosis but not the module status,
the status 01B ”Module fault” is entered for a faulty identifier.
If an underlying slave delivers neither its own module status nor a module
diagnosis, the status is entered as follows:
– For error-free operation: 00
B
”Module OK”
– For configuration error: 10
B
”Incorrect module”
– For missing slave: 11
B
”No module”
– For all other errors (e.g. “Prm_Fault”): 01
B
”Module faulty”
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...