DP Slaves Connectable to a Y Link
C-3
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
Table C-3
CPUs that can be used as I slaves with various I/O ranges
Slave name
Path
1)
Device master
file
Input bytes
Output
bytes
Number of
slaves
2)
S7-300 CPU 315-2DP
(...-2AF01-... or
...-2AF02-...)
SPS\SIMATIC
Siem802f.gs*
Max. 122
Max. 122
1
3)
S7-300 CPU 315-2DP
(...-2AF03-... )
SPS\SIMATIC
Sie3802f.gs*
Max. 244
Max. 244
1
3)
S7-300 CPU 316-2DP
SPS\SIMATIC
Siem806f.gs*
Max. 244
Max. 244
1
3)
S7-300 CPU 318-2DP
SPS\SIMATIC
Siem807f.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 412-1
SPS\SIMATIC
Siem80c5.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 412-2
SPS\SIMATIC
Siem80c6.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 414-2
SPS\SIMATIC
Siem80c7.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 414-3
SPS\SIMATIC
Siem80c8.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 416-2
SPS\SIMATIC
Siem80ca.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 416-3
SPS\SIMATIC
Siem80cb.gs*
Max. 244
Max. 244
1
3)
S7-400 CPU 417-4
SPS\SIMATIC
Siem80cc.gs*
Max. 244
Max. 244
1
3)
1)
In the hardware catalog based on “PROFIBUS-DP\Additional FIELD DEVICES”
2)
Number of slaves of the same kind that exhaust the capacity of the I/O quantity structure of the Y link
3)
Applies when the maximum number of slaves is installed
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...