Commissioning the DP/PA Link
6-2
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
6.1
Commissioning the DP/PA link
Prerequisites
The following prerequisites must be met before you commission the DP/PA link:
You must have completed the setup and wiring of the DP/PA link as described
in Sections 3 and 4.
You must have completed the setup of PROFIBUS-DP. PROFIBUS-DP must be
ready for operation.
You must have completed the setup of PROFIBUS-PA. PROFIBUS-PA must be
ready for operation.
Commissioning the DP/PA link
Step
Activity
1
Configure the DP/PA link.
2
Set the PROFIBUS address of the IM 157.
3
Switch on the power supply for the DP/PA link.
4
Load the configuration into the target system.
Configuring the DP/PA link
The DP/PA link is configured with STEP 7 for S7 standard operation and for
redundant operation.
For the DP standard master operation, the DP/PA link is configured via the
device master file, e.g. with COM PROFIBUS.
The DP/PA couplers are gateways between the S7 backplane bus of the IM 157
and PROFIBUS-PA with the PA field devices. Therefore, the DP/PA coupler does
not have to be configured.
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...