Diagnostics Using the User Program
10-11
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
Byte x+36
82
H
Continued from the previous page
Status of the IM 157
Status of the IM 157, see table below
Byte x+37
Identifier for the configured order number
(BCD-coded)
Byte x+38
Reserved
Byte x+39
Reserved
Byte x+40
Reserved
Byte x+41
IM 157 hardware version
Byte x+42
IM 157 firmware version
Byte x+43
Bit no.
1: Start-up delay enabled
7 6 5 4 3 2 1 0
0 0 0
0: At least one slave not is engaged in data exchange
with the IM 157.
1: All slaves are engaged in data exchange with the
IM 157
1: Missing or incorrect configuration
1: Invalid bus parameter for PROFIBUS-DP
Overview of channel diagnosis
Byte x+44
Byte x+45
Byte x+58
Byte x+59
.
.
If a bit is set, this indicates that the slave with the corresponding address
reported a channel-related diagnosis.
0
Bit no.
7
6
5
4
3
2
1
0
Addresses 3 to 7
.
.
.
.
.
.
Addresses 112 to 119
7
6
5
4
3
–
–
–
119 118
117 116
115 114
113 112
Addresses 8 to 15
Addresses 120 to 125
–
–
125 124 123 122 121 120
15
14
13
12
11
10
9
8
Figure 10-6
Structure of the status message, continued
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...