DP Slaves Connectable to a Y Link
C-2
DP/PA Link and Y Link Bus Couplings
A5E00193841-011
Restrictions
In the underlying DP master system, operator panels and text displays can only
be operated as DP slaves and not as active bus nodes.
Slaves in the DPV1 mode cannot be operated in the underlying DP master
system if the Y link is in DPV0 mode (DP master in “S7-compatible” mode).
Configuration of S7-300/S7-400 stations as I slaves
The CPU for an S7-300 or S7-400 station cannot be used out of the “preconfigured
stations” catalog directory but must be integrated via the device master file.
When configuring the S7-300/S7-400 station, a “dummy” DP system must be
created that has the same bus settings (transmission rates, etc.) as the underlying
DP master system of the Y link but not the same bus name. The station number of
the S7-300/S7-400 must coincide with the slave address on the Y link.
Examples of usable DP slaves
The table below shows a selection of field devices that can be defined via the
device master file as DP slaves. It also presents all of the S7-CPUs that can be
used as I slaves with various I/O ranges.
Table C-2
Examples of usable DP slaves
Slave name
Path
1)
Device master
file
Input bytes
Output
bytes
Number of
slaves
2)
Gateway 3WN6
Switchgear
Siem8032.gs*
Max. 12
Max. 12
20
3)
ET 200X with BM147/CPU
as I slave with various I/O
ranges
I/O\ET200X
Siem804a.gs*
Max. 244
Max. 244
1
3)
SIMOCODE-DP with the
Type 1 Compact basic
module
Switchgear
\SIMOCODE
Siem8031.gs*
12
4
20
SIMODRIVE 611U
with 1 axis, PPO Type 5
Drives
\SIMODRIVE
Siem8055.gsd
28
28
8
SIMODRIVE 611U
with 2 axes, PPO Type 5
56
56
4
SIMODRIVE POSMO A
Drives
\SIMODRIVE
Siem8054.gsd
12
12
20
Heating control HS 724
General
\OTHER
Siem002b.gsd
32
32
7
1)
In the hardware catalog based on “PROFIBUS-DP\Additional FIELD DEVICES”
2)
Number of slaves of the same kind that exhaust the capacity of the I/O quantity structure of the Y link
3)
Applies when the maximum number of slaves is installed
Содержание Simatic 6ES7 157-0AC80-0 A0 Series
Страница 14: ...Contents xiv DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 42: ...Installation 3 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 70: ...Commissioning the DP PA Link 6 12 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 162: ...Technical Specifications B 40 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 170: ...Order Numbers and Accessories D 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 178: ...Glossary Glossary 8 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...
Страница 182: ...Index Index 4 DP PA Link and Y Link Bus Couplings A5E00193841 01 1 ...