66
SICAM Q80 7KG8080
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
5.1.3.2.3 Automatic restart upon power outage
SICAM Q80 7KG8080
has a number of features intended to ensure uninterrupted monitoring.
1. The device's built-in UPS secures continued measurement operation despite short-term failure of the power
supply.
2. The device's automatic self-starting capability enables continuation of measurement following either a longer-
term power outage or continual short outages: if the internal rechargeable battery's capacity is insufficient, the
current measurement ends automatically. In this case, proper closure of all measurement files is ensured.
Option „
Always assimilate parameters to the current settings
“
Activated: Prior to "
Send+Start
", the system checks whether the new parameters match those of the
Autostart. If not, the automatic start is re-initialized. This ensures that measurement starts with the same
settings every time after occurrence of a power outage.
Inactive
: The Autostart starts with the parameters as they had been set at the time of the initialization. Any
changes to the settings which were subsequently transmitted to the device using "
Send
" or "
Send+Start
" are
ignored.
The automatic starting mode can also be used to prepare and test a measurement at the office. When
SICAM Q80
7KG8080
is subsequently hooked up at the measurement site and activated, measurement can begin without any
further configuring.
The button
Initialize
writes the current setting to the device a single time.
Note
After initialization, these measurement settings are in effect until the removable data carrier
is totally cleared or the configuration is deleted.
Regardless what other measurements are performed in the meantime, upon activating the
device, exactly this measurement is started again.