53
Operation modes and settings
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
Separate summation of the active power provided per averaging interval
Separate summation of the capacitive and inductive reactive power per averaging interval
By default, the calculation is deactivated.
Reference
SICAM Q80 7KG8080 Instruction manual:
Computations > Basics > Measurement types
5.1.2.3.5 Trigger digital SICAM Q80 7KG8080
Triggers can also be defined by external events. This can be transported as network bits as well as be based on the
device’s own digital inputs (optionally).
Triggering via digital IN:
If the device possesses digital inputs, then triggers can be configured to respond when a signal transition occurs at
the digital input. All available digital inputs are displayed, in accordance with how the measurement device is
equipped.
Name:
text
Anything except / \ : * ? < > |
Status:
Active/passive
(De)-activation of the monitoring of a digital input
Trigger condition:
0
1 / 1
0
Definition of the signal transition to be monitored
LED shines:
Green - the high level is applied at the DI
Yellow - High level recognized, but + and – were mistakenly switched in the wiring. The DI DOES NOT go to
High level! There is no state transition and thus no trigger release.