176
SICAM Q80 7KG8080
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
Other commands:
Set defaults:
Sets the default paths.
Set example data:
Sets the default paths for installation of the sample data.
Note
The path for measured data can be changed independently of the database folder.
Comparisons of measured data saved in different databases are not possible.Start: Global
option upon starting the program.
The paths for the data and database must be enabled (reading- + writing rights)
6.3.4.1.2 Options - Setup
Options - Setup
If the option
Use normtest settings
is active, the measurement is only used in compliance with the standard IEC
61000-4-30. Other measurement quantities are not investigated.
For instance, in this case, no current measurement is performed. The aggregation interval is set permanently to 10
min. Additionally, the aggregation over 3s, 10min and 2h are displayed.
Note
If this option was selected during installation of the software, additional
are
available.
6.3.4.1.3 Options - Start
Global option upon starting the program.
Program start settings
Upon starting
SICAM Q80 Manager
, the configuration last used is loaded automatically.
Class A measurement device as per the standard 61000-4-30 (Among other things: measurement start only
at multiples of 10 minutes. If a radio clock is used, data originating from different measurement devices can
be compared sample-by sample.)
73