RUGGEDCOM MX5000RE
Installation Guide
Chapter 2
Installing the Device
Installing the Chassis Ground Connection
13
1
2
3
Figure 6: AC Terminal Block Wiring
1.
Live Terminal
2.
Ground Terminal
3.
Neutral Terminal
1
2
3
Figure 7: DC Terminal Block Wiring
1.
Live Terminal
2.
Ground Terminal
3.
Neutral Terminal
5. Connect the neutral (-/N) lug from the PS1 cable assembly to the neutral terminal on the PS1 terminal block.
IMPORTANT!
If the ground terminals are not connected to safety Earth, the chassis ground connection must be
connected. For more information, refer to
Section 2.4, “Installing the Chassis Ground Connection”
6. Connect the ground (GND) lug from the PS1 cable assembly to the ground terminal on the PS1 terminal block.
7. If necessary, repeat
to connect the PS2 cable assembly.
8. Install the inner and outer safety covers, making sure the cables pass through the openings in the sides of the
covers.
9. Secure the inner and outer supply safety covers with the screws removed in
Section 2.4
Installing the Chassis Ground Connection
If the ground terminal on the power supply module(s) is not connected to safety Earth, a connection must be
provided from the chassis ground terminal on the RUGGEDCOM MX5000 chassis.
Содержание RUGGEDCOM MX5000RE
Страница 4: ...RUGGEDCOM MX5000RE Installation Guide iv ...
Страница 10: ...Preface RUGGEDCOM MX5000RE Installation Guide x Customer Support ...
Страница 18: ...Chapter 1 Introduction RUGGEDCOM MX5000RE Installation Guide 8 Decommissioning and Disposal ...
Страница 38: ...Chapter 2 Installing the Device RUGGEDCOM MX5000RE Installation Guide 28 Connecting Power to the Enclosure ...
Страница 52: ...Chapter 4 Modules RUGGEDCOM MX5000RE Installation Guide 42 Installing Removing Power Supply Modules ...
Страница 56: ...Chapter 5 Technical Specifications RUGGEDCOM MX5000RE Installation Guide 46 Dimension Drawings ...