Power Supply Specifications
Input Range
Power Supply Type
Min
Max
Internal Fuse Rating
Max. Power
Consumption
a
HI (125/250 VDC)
b
88 VDC
300 VDC
HI (110/230 VAC)
b
85 VAC
264 VAC
6.3 A, 250 V(T)
c
110 W
d
a
Power consumption varies based on the device configuration. Each 10/100Base-Tx port consumes roughly 1 W less than a fiber optic port.
b
The HI power supply is the same power supply for both AC and DC.
c
(T) denotes time-delay fuse. Internal fuse is not user-replaceable.
d
Rating at 85 °C (185 °F) ambient temperature at worst-case load.
Section 5.2
Failsafe Relay Specifications
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
2 A, 60 W
125 VDC
0.24 A, 30 W
125 VAC
0.5 A, 62.5 W
220 VDC
0.24 A, 60 W
250 VAC
0.25 A, 62.5 W
1500 V
rms
for 1 minute
Содержание RUGGEDCOM MX5000RE
Страница 4: ...RUGGEDCOM MX5000RE Installation Guide iv ...
Страница 10: ...Preface RUGGEDCOM MX5000RE Installation Guide x Customer Support ...
Страница 18: ...Chapter 1 Introduction RUGGEDCOM MX5000RE Installation Guide 8 Decommissioning and Disposal ...
Страница 38: ...Chapter 2 Installing the Device RUGGEDCOM MX5000RE Installation Guide 28 Connecting Power to the Enclosure ...
Страница 52: ...Chapter 4 Modules RUGGEDCOM MX5000RE Installation Guide 42 Installing Removing Power Supply Modules ...
Страница 56: ...Chapter 5 Technical Specifications RUGGEDCOM MX5000RE Installation Guide 46 Dimension Drawings ...