3.3.2 Setting and readjusting setpoints
Room temperature setpoints can be …
– set during commissioning,
– readjusted during operation.
The source can be …
– the local HMI,
– a tool,
– a central control unit.
The thermostat stores the setpoints …
– in EEPROM in the form of parameters,
– in the runtime memory.
The table below shows the interrelations:
Setpoint setting
Stored in EEPROM
of thermostat
Commissioning
– HMI
– Tool download
Input LTE-Mode
Input S-Mode
Comfort basic setpoint
Dead zone Comfort
1)
Setpoints Heating
Setpoints Cooling
Comfort basic setpoint
P08 Comfort basic setpoint
P33 Dead zone Comfort
1)
Setpoint Economy Heating
Setpoint Economy Cooling
Setpoints Heating
Setpoints Cooling
Setpoints Heating
Setpoints Cooling
P11 Economy Heating
P12 Economy Cooling
Setpoint Protection Heating
Setpoint Protection Cooling
P65 Protection Heating
P66 Protection Cooling
Current runtime
setpoints in
thermostat
Setpoint adjustment
New current
runtime setpoints
in thermostat
Input LTE-Mode
2)
Input S-Mode
3)
Local ope-
ration
3)
Comfort setpoint
Setpoint shift H
Setpoint shift C
Comfort setpoint Rotary knob
Comfort setpoint
Economy Heating
Economy Cooling
Setpoint shift H
Setpoint shift C
Economy Heating
Economy Cooling
Protection Heating
Protection Cooling
Protection Heating
Protection Cooling
Effective room operating mode
Current setpoint
(used by the thermostat for temperature control)
1)
Only required for heating AND cooling applications (see section 3.6.9)
2) The shift is added to the local shift (LTE-Mode only)
3) The last intervention wins, either S-Mode input or local operation
4)
To display the S-Mode objects of the Economy heating and cooling setpoint (P11, P12), set the
control parameter "Room temperature: Economy setpoints" to
as group object
in the ETS tool
The current setpoint (used by the thermostat for temperature control) is available
on the bus for use in the central control unit.
KNX
R
Comfort basic setpoint
Comfort setpoint
Economy heating
setpoint
4)
Economy cooling
setpoint
4)
KNX
R
Current setpoint