5.2.3 Operation and monitoring with OZW772
.
The OZW772 web server enables users to operate a Synco HVAC system from
a remote location – via PC or from a smartphone via the web. A start page
shows the most important data points. A combination of menu/path navigation
enables users to access all data points quickly and straightforwardly. The entire
installation can be visualized in the form of plant diagrams. Alarm and state
messages can be forwarded to different message receivers, such as e-mail,
SMS, etc.
For details, refer to Commissioning Instructions CE1C5701.
6. Connection
6.1 Connection
terminals
SELV
G
X1 M
G0
Y1
U1
31
92
A
0
1
CE+ CE -
D1 GND
Y2
Y10
G, G0
Operating voltage AC 24 V
Y10-G0
Control output for DC 0…10 V actuator
Y1-G, Y2-G Control outputs for 2-position, PWM or 3-position
actuators
X1
Multifunctional input for temperature sensor (e.g.
QAH11.1) or potential-free switch
Factory setting: External temperature sensor
(function can be selected via P38)
M
Measuring neutral for sensors and switches
U1
DC 0…10 V input for actual air damper position
DC 0…10 V input for CO
2
sensor (0…2000 ppm)
(RDG405KN)
(Note: G0 is the measuring neutral for U1!)
D1-GND Multifunctional input for potential-free switch.
Factory setting: Operating mode switchover contact
(function can be selected via P42)
CE+
KNX data +
CE-
KNX data –