3.13.2 Parameter setting/download via tool
Control parameters can be adjusted via bus either by parameter download
during commissioning or during normal operation with a tool like the ACS.
With the ACS tool, the parameters can be changed …
– during commissioning via parameter download (all parameters),
– during normal operation via Popcard (most parameters).
Most parameters can be changed during normal operation using the OZW772
web server.
Only the parameters for the device address can be downloaded via ETS. This is
to simplify matters and to avoid conflicts.
It allows you to further engineer communication objects of an RDG.. previously
commissioned via local HMI or the ACS tool (assigning communication objects
to group addresses).
∂
The basic application can only be changed via parameter download with the
ACS tool
∂
The RDG..KNX room thermostats require version ETS4 or higher/ACS790
The connection of a KNX commissioning/operating tool to the RDG.. is
described in section 4.2.
ACS
OZW772 web server
ETS
Notes
Connecting a KNX tool