21 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
Function if no time schedule is received via bus
User profile for operating mode
(selected via P02)
Operating mode
when activating
function
Function
Operating
mode
during
function
Operating
mode at
the end of
function
P02 = 1:
Comfort
Extension
Comfort
Protection
Comfort
Absence
Protection Comfort
P02 = 2:
Comfort or Economy Extension
Comfort
Economy
Comfort or Economy Absence
Economy Comfort
Extension/absence functions are not available in Protection mode.
Function with time schedule via bus
User profile for operating
mode
(selected via P02)
Operating mode when
activating function
Function
Operating
mode
during
function
Operating
mode at
the end of
function
P02 = 1:
Auto or Comfort
Extension
Comfort
Auto
Auto or Comfort
Absence
Protection Auto
P02 = 2
⇓
Auto, Comfort or Economy Extension
Comfort
Auto
Auto, Comfort or Economy Absence
Economy Auto
Extension/absence functions are not available in Protection mode.
3.2.2 Communication examples
The following examples show 2 typical applications of a central time schedule in
connection with local control of the room operating mode.
The room operating mode in rooms 1…2 of a building is determined by the time
schedule
.
Window contacts are fitted in all rooms.
The following conditions are specified:
The rooms are used and controlled by the time schedule as follows:
– Night setback from 17:00 to 08:00 (Economy)
– Protection from 20:00 to 06:00
– Lunch break from 12:00 to 13:00 (Precomfort)
The substitution (P88) for Precomfort via bus is set on the thermostat as follows:
– Room 1: Comfort (1)
– Room 2: Economy (0)
Note
Note