Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
3.7.4 Control outputs configuration (setting via DIP
switches 4 and 5 or tool, and P46…P47)
Control outputs
Application
O
n
/O
ff
(2
-p
o
s
it
io
n
)
M
o
d
u
la
ti
n
g
P
W
M
(2
-p
o
s
it
io
n
)
M
o
d
u
la
ti
n
g
3
-p
o
s
it
io
n
M
o
d
u
la
ti
n
g
D
C
0
…
10
V
M
o
d
u
la
ti
n
g
K
N
X
Single-duct
Single-duct and electric heater
Single-duct and radiator/floor heating
Single-duct heating/cooling coil
The function of the control outputs is set via DIP switches 4 and 5:
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
ON
OFF
1
2
3
4
5
31
81
D
10
1
DIP 4: Y10 =
DC 0…10 V
DC 0…10 V
DC 10…0 V
(inverted)
DC 10…0 V
(inverted)
DIP 5: Y1/Y2 =
2-position
3-position
2-position
3-position
Y1-Y2:
∂
If 2-position is selected, the factory setting is On/Off.
If PWM is required (pulse width modulation), P46 must be set to 2 = PWM
P47:
∂
0 = VAV box: DC 0…10 V control signal or KNX LTE-Mode
∂
1 = VAV box: 3-position control signal
All DIP switches must be set to OFF if the application is commissioned via tool. In
this case, the control outputs must be set via the ACS tool.
For details concerning connection of peripheral devices and setting of the DIP
switches, refer to the Mounting Instructions M3192 [3].
Single-duct with 3-position damper actuator:
ON
OFF
1
2
3
4 5
P47 = 1
Application
Y1/Y2 =
3-position
Control output
VAV = 3-position
Notes
Example