84 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
8. Technical
data
Operating voltage
SELV AC 24 V
°
20%
Rated voltage
AC 24 V
Frequency
50/60 Hz
Power consumption
Max. 2 VA/1 W
No internal fuse!
In all cases, external preliminary protection with
a circuit breaker max. C 10 A is required.
Control output Y10-G0
Resolution
Current
DC 0…10 V
39 mV
Max.
°
1 mA
Control output Y1, Y2-G
Rating
AC 24 V
Max. 1 A
Power limitation
3 A fast microfuse
(cannot be exchanged)
Multifunctional inputs
X1-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
U1-G0
Input for actual air damper position
feedback
damper position 0%(fully closed)
100% (fully open)
Input for external CO
2
/VOC sensor
(RDG405KN)
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
QAH11.1 (NTC)
0...49 °C (32…120 ˚F)
Max. 80 m
Selectable (NO/NC)
DC 0…5 V, max. 5 mA
Max. 20 thermostats per
switch.
Do not mix with D1!
DC 0…10 V, max. 0.3 mA
0…100%
DC 0…10 V, max. 0.3 mA
0… 2000 ppm
Selectable (NO/NC)
SELV DC 6…15 V, 3…6 mA
Max. 20 thermostats per
switch.
Do not mix with X1!
Function of inputs
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable
electric heater contact, fault contact, monitoring
input
Selectable
X1: P38
D1: P42
Interface type
KNX, TP1-64
(galvanically separated)
Bus current
20 mA
Bus topology: Refer to KNX Manual (see reference documentation)
Switching differential (adjustable)
Heating mode
(P30)
Cooling mode
(P31)
2 K (0.5...6 K)
1 K (0.5...6 K)
Setpoint setting and setpoint range
Comfort
(P08)
21 °C (70 ˚F) (5…40 °C) (41…104
Power supply
Outputs
Inputs
KNX bus
Operational data