3.6.8 Single-duct applications with heating/cooling coil
On single-duct applications with heating/cooling coil, the thermostat controls an
actuator (air damper, VAV system, etc.) plus a heating/cooling water coil.
The output signal for the air flow can be limited to a minimum and maximum value
if required (see section 3.4.1).
The thermostat controls the reheating/cooling water valve either in heating/cooling
mode with changeover (automatically or manually), heating only, or cooling only.
Cooling only is factory-set (P01 = 01).
The air flow starts to rise depending on the acquired room temperature, the current
supply air temperature (if available) and the setpoint.
If the room temperature is above the setpoint for cooling (w), the valve receives an
Open
command and the air flow signal starts to rise to maintain the room
temperature setpoint.
If the room temperature drops below the setpoint for heating (w), the valve receives
an
Open
command.
The diagrams below show the control sequence for modulating PI control in
Comfort mode.
2-position heating/cooling coil
Modulating heating/cooling coil
Y
YHC
TR [
癈
]
SDC
C
H
dz
m
ax
m
in
Y
0%
100%
TR [
癈
]
XpC
YV
C
H
Vmin
Vmax
XpH
Changeover water
YHC
ON
OFF
w
SDH
Changeover air
(w)
Y
0%
100%
YHC
TR [
癈
]
XpH
w
XpC
YHC
C
H
dz
m
ax
m
in
Y
0%
100%
TR [
癈
]
XpC
YV
C
H
Vmin
Vmax
XpH
Changeover water
Changeover air
(w)
Y
Output signal
TR
Room temperature
w
Comfort setpoint when heating sequence active
(w)
Comfort setpoint when cooling sequence active
H
Heating sequence
C
Cooling sequence
YV
Volume flow rate
XpH Proportional band heating
XpC Proportional band cooling
Vmin Minimum volume output
Vmax Maximum volume output
SDH Switching differential heating
Water coil valve in
cooling mode
Water coil valve in
heating mode
Control sequence