3.13.3 Parameters of the Service level
P
ar
am
et
er
Name
Factory setting
Range
R
D
G
40
0K
N
R
D
G
40
5K
N
D
ep
en
d
en
ci
es
Service level
P01 Control
sequence
1 = Cooling only
0 = Heating only
1 = Cooling only
2 = H/C changeover manual
3 = H/C changeover auto
P02
Operation via room op selector
1
1 = Auto - Protection
2 = Auto - Comfort - Economy -
Protection
P04 Unit
C (0)
C = degrees Celsius
F = degrees Fahrenheit
P05
Measured value
correction
0 K
– 3...3 K
P06 Standard
display
0
0 = Room temperature
1 = Setpoint
P07
Additional display
information
RDG400KN (range 0...4)
RDG405KN (range 0...4, 6,7)
0
0 = --- (no display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12 h) (via bus)
4 = Time of day (24 h) (via bus)
6 = CO
2
concentration [ppm]
7 = CO
2
symbols
P08
Comfort
basic setpoint
21 °C
5...40 °C
P09
Comfort
setpoint minimum
5 °C
5...40 °C
P10
Comfort
setpoint maximum
35 °C
5...40 °C
P11
Economy
heating
setpoint
15 °C
OFF, 5...WCoolEco;
WCoolEco = 40 °C max.
P12
Economy
cooling
setpoint
30 °C
OFF, WHeatEco...40 °C;
WHeatEco = 5C min.
P14 Button
lock
0
0 = Unlocked
1 = Auto lock
2 = Manual lock
P19 CO
2
(VOC) Setpoint
1000
OFF(0)…5000 ppm
X
P20 CO
2
(VOC) P-band Xp
400
10…2000 ppm
X
Parameter display depends on selected application and function.
Note