29 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
3.4 Applications
overview
The room thermostats support the following applications, which can be configured
using the DIP switches at the rear of the unit or a commissioning tool.
DIP switches 1...5 must be set to OFF (remote configuration, factory setting) to
select an application via commissioning tool. In this case, the output signal type
needs to be set in the ACS tool as well.
The tool offers the applications printed in bold text (basic applications).
Application
DIP switches
Remote configuration
Via commissioning tool (factory setting)
∂
Synco ACS
∂
ETS
1
ON
2
3
OFF
4
5
Single-duct
∂
DC 0…10 V damper actuator (P47 = 0)
∂
3-position damper actuator (P47 = 1)
∂
VAV compact controller KNX LTE mode
31
92
S
0
7
B1
T
M
V
M
V
YV
1
ON
2
3
OFF
4
5
Single-duct with electric heater
∂
DC 0…10 V damper actuator and On/Off,
PWM or 3-position electric heater (P47 = 0)
∂
3-position damper actuator and
DC 0…10 V electric heater (P47 = 1)
∂
VAV compact controller KNX LTE-Mode
and electric heater
31
92
S
0
8
YE
B1
T
M
V
M
V
YV
1
ON
2
3
OFF
4
5
Single-duct and radiator/floor heating
∂
DC 0…10 V damper actuator and On/Off,
PWM or 3-position radiator (P47 = 0)
∂
3-position damper actuator and
DC 0…10 V radiator (P47 = 1)
∂
VAV compact controller KNX LTE-Mode
and radiator
31
92
S
0
9
M
V M
V
YV
YR
B1
T
1
ON
2
3
OFF
4
5
Single-duct heating and cooling coil
∂
DC 0…10 V damper actuator and On/Off,
PWM or 3-position heating and cooling
(P47 = 0)
∂
3-position damper actuator and
DC 0…10 V heating and cooling
(P47 = 1)
∂
VAV compact controller KNX LTE-Mode
and heating/cooling coil
31
92
S
11
(B1)
T
(B1)
M
V
M
V
YV
Y1
T
1
ON
2
3
OFF
4
5
- P47 is used to change the air damper output from DC 0...10 V (factory setting) to
3-position
- P46 is used to change the valve output from On/Off (factory setting) to PWM
Notes