64/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Basic communication settings
30.08.2007
6.1.4
Remote reset of fault
The "Remote reset of fault" function is used to reset the Synco 700 RM… controller
faults transmitted over the KNX bus and requiring "Acknowledgement and reset", to
be acknowledged (and reset if "Remote reset fault: Yes") with the OCI700.1 service
tool, the RMZ792 bus operator unit and the OZW775 central communication unit.
Main menu > Commissioning > Communication > Basic settings
Remote reset faults for the RM… controllers
Default.
No
Settings
No/Yes
Apart from the RMH760 heating controller, all RM… controllers (including the
RMH760B heating controller) incorporate the "Remote reset of fault" function.
RM… controllers
Note
Basic settings
Dec bus power supply: On
Clock time op: Slave
Rem set clock save: Yes
Remote reset fault: Yes