28/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Commissioning notes
30.08.2007
Main menu > Commissioning > Communication > Basic settings
Before modifiable values are changed for the first time, the operating lines show
the factory-set values, e.g. device address 255.
The factory-settings are also referred to as standard or default values.
3.2.2 Terminating
commissioning, plant mode "Auto"
If the plant mode was set to "Plant operation = Off" at the start of commissioning
(see section 3.2.1), it must be reset to "Plant operation = Auto" when
commissioning is complete.
When commissioning is complete (e.g. after "Basic settings", see the operating
page above), the repeated pressing of the ESC button results in the following
warning:
Acknowledge the display of
OK
by pressing the knob (the plant will start). The
display then reverts to the main menu.
Before leaving the main menu, press the knob to open the "Plant operation" page.
Select "Auto" (= enable) on the "Preselection" line and acknowledge by pressing
the knob. Press ESC to return to the start page.
Basic settings
Notes
Plant starting
Action
Plant operation = Auto
Action
Basic settings
Device address: 255
Dec bus power supp: On
Clock time op: Master
Rem set clock slave: Yes
Caution!
Plant starts
ESC
OK
Main menu
Commissioning...
Time switch...
Room operating mode...
Plant operation...
Plant operation
Preselection: Auto
State: On
Cause: User request room