52/120
Building Technologies
Basic documentation: Communication via the KNX bus
CE1P3127en
HVAC Products
Device addresses via ACS
30.08.2007
1. In ACS Service select
Plant > Edit device list…
to open the "Edit device list" dialog
box (see section 5.2.1).
2. Select the room unit with the left mouse button and click the button
marked
Manually…
to open the "Address assignment" dialog box.
3. Enter a device address in the range 1…253 (excluding 150), and confirm by
clicking the
Write
button.
1. Set the room unit
locally
to programming mode. To do this, press the presence
button for approximately 12 seconds. The display reads
Prog.
2. In ACS Service select
Plant > Edit device list…
to open the "Edit device list" dialog
box (see section 5.2.3). Click the
Programming mode…
button to open the "Address
assignment" dialog box.
3. Enter a device address in the range 1…253 (excluding 150), and confirm by
clicking the
Write
button.
When the new device address has been adopted, the room unit reverts to a
display of the room temperature.
The room unit only switches to programming mode if the bus power is available.
Assigning addresses
manually
Programming mode
Bus power