Device address and device name
30.08.2007
With access at the Service level, the setting values on the "Basic settings" page
are read-only values. This is indicated by the fact that the highlight bar does not
cover the whole operating line, i.e. the settings themselves are not highlighted.
In small networks, the KNX bus can be commissioned with the factory-set area
address 0 (zero) and line address 2. These addresses are permissible only if:
•
The Synco bus devices are installed in Area 0 and Line 2 of a network, and not
assigned to other areas and lines by means of super-ordinate area and line
couplers.
The other basic settings under "Communication" can be read by rotating the knob
clockwise.
4.1.2
Assigning device names
The RMZ790 and RMZ791 operator units can be used to assign an individual
device name (e.g. plant name) to every RM… controller. This device name is
displayed on the second line of the start page in the RMZ790 and RMZ791
operator units.
On delivery from the factory, the word "Welcome" is displayed instead of the device
name.
Communication
Basic settings
Notes
Reading other
basic settings
Start page
Basic settings
Area:
0
Line: 2
Device address: 255
Dec bus power supp: On
Basic settings
Dec bus power supp: On
Clock time op: Master
Rem set clock slave: Yes
Remote reset fault:
No
Wednesday 28.05.2003
15:06
Welcome
« Information
Main menu »
Communication
Basic settings…
Room…
Holiday/Special days
Distribution zone…