6AW5451-6XX01-1K
ES 030-K Manual
Subject to change without prior notice
3 - 29
RD: 08.2000
(4)J31069-D0136-U001-A0-7618
3.4.4.4 MOBY-L
Connection 1
The tasks for MOBY are to be defined in a command list
compiled by the user. Each task can consist of a command or a
command chain. On a command chain, the commands will
continue to be processed as long as the identifier "further
command follows" is set.
Setting the Parameters in DB 1
Address of the list
of commands
Error (general)
Supplied by
DB 1
DW 53
User
DB 1
DL 54
System
Error in MOBY
module
DB 1
DR 54
System
Parameter
Address
Structure of a Task
Command (1)
Byte count (1)
MDS address (1)
DB (1)
DW (1)
Command (2)
Byte count (2)
MDS address (2)
DB (2)
DW (2)
Byte count
1 to 250; number of bytes that are to be
transferred with this command.
MDS address 0 to 506; address of the beginning of
the data on the MDS.
DB, DW
Address where the data begins on the
ES 030-K.
Structure of the Command
“
MDS address", the size of the
memory must be parameterized
Bit 7 6 5 4 3 2 1 0
Read command
Write command
Initialise command in the DW
Further command follows;
chaining of several commands for one MDS processing. This bit must
be 0 on the last command.
128 Byte
0080
512 Byte
0200
FY 16/17 Assignment
Bit 7 6 5 4 3 2 1 0
Task initiation
Acknowledge
Error
RESET initiation
Initiation:
Set by the user. The system will reset the flag and set the acknowledge flag.
Acknowledge:
Set by the system after task has been performed. Reset by the user and by the system upon new
initiation.
Error:
Set by the system. Exact description of errors is in DB 1 DW 54/56 (see also chapter 3.2.1).
RESET:
Set by the user. Reset by the system after execution. A command being executed will be
cancelled by the error message
“
RESET executed". For a RESET command, the flags 16.3
(17.3) and 16.0 (17.0) must be set simultaneously. The RESET signal is always acknowledged
with the error flag 16.2 (17.2).
ECC operation:
Set by the user. If flag 16.5 (17.5) is set to
“
1", processing will be carried out with ECC (Error
Correction Code); if set to
“
0", processing will be without ECC.
ANW:
Set by user. If flag 16.6 (17.6) is set to
“
1", processing will be carried out with presence; if reset to
“
0", without presence. At the same time, bit 16.0 (17.0) as well as bit 16.3 (17.3) must be set.
ANW bit:
Set by the system. If flag 16.6 (17.6) is set, flag 16.7 (17.7) indicates whether data memory (MDS)
is present in the field or not.
ECC operation: ON/OFF
Presence check: ON/OFF
ANW bit : 1 = MDS in field
Connection 2
The structure of the MOBY-L connection 2 is analogous to the structure of connection 1. DW 53 and 54 are simply replaced by
DW 55 and 56, and FY 16 is replaced by FY 17.