Appendices
Appendix E – Modbus VERIS H8035/H8036 Emulation
96
Building Technologies
125-202
06/06/2017
Modbus
Register
Offset
ViewPoint Name
Description
40005
4
kVA System
System Apparent Power (kVA)
40006
5
Apparent PF System
System Apparent Power Factor (PF)
40007
6
Volts Line to Line Avg
Average Line to Line Voltage
40008
7
Volts Line to Neutral Avg
Average Line to Neutral Voltage
40009
8
Amps System Avg
Average current of all phases
40010
9
kW L1
Individual Phase True Powers (kW, 3 values)
40011
10
kW L2
"
40012
11
kW L3
"
40013
12
Apparent PF L1
Individual Phase Apparent Power Factors (PF, 3
values)
40014
13
Apparent PF L2
"
40015
14
Apparent PF L3
"
40016
15
Volts L1 to L2
Individual Phase to Phase Voltages (Volts, Delta, 3
values)
40017
16
Volts L2 to L3
"
40018
17
Volts L1 to L3
"
40019
18
Volts L1 to Neutral
Individual Phase to Neutral Voltages (Volts, Wye, 3
values)
40020
19
Volts L2 to Neutral
"
40021
20
Volts L3 to Neutral
"
40022
21
Amps L1
Individual Phase Currents (Amps, 3 values)
40023
22
Amps L2
"
40024
23
Amps L3
"
40025
24
kW System Avg
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable)
40026
25
kW Demand System Min
System Minimum Demand (kW, resettable), It displays
the default value after a CAM until 1 demand window
elapses. After a power cycle or CPU reset, the value is
not reset and does not update again until 1 demand
window elapses.
40027
26
kW Demand System Max
System Maximum Demand (kW, resettable). Behaves
as 40026.