Prepping for Installation
Connecting a Communication Cable
26
Building Technologies
125-202
06/06/2017
Keep in mind that the Ethernet connection must have an IP address in the ViewPoint
software that can either be set manually within the software with the Use Static IP
Address option (for a fixed address) or obtained automatically from the router
connected to the logger using the Use DHCP option (dynamic address). Both options
have advantages, see
About IP Addresses.
NOTE:
When Ethernet is connected, any RS-485 connection is deactivated. To activate the
RS-485 interface, the MD-BMS or MD-BMED Power Meters must be power cycled
with the Ethernet cable removed.
1. Select Ethernet (TCP/IP) to gather information using a network connection. When
selected, the Communications Setup screen changes, and an IP address is
required as address switches are ignored.
2. Select your mode of communication.
3. Do one of the following:
●
Enter the IP address for the Ethernet connection of the meter or select one of the
previously used addresses from the drop-down list. See
About IP Addresses.
●
Use the Scan Network or Setup buttons to acquire a new IP address. See
About IP
Addresses.