Appendices
Appendix A - MD-BMS and MD-BMED Power Meters BACnet Analog Value Objects
68
Building Technologies
125-202
06/06/2017
Object
Identifier
Name
Description
7050
kVAh L2 Positive
"
7060
kVAh L2 Negative
"
7080
kVAh L3 Positive
"
7090
kVAh L3 Negative
"
8000
kVA System
System Total Apparent Power (kVA). Unsigned absolute value of (kVA L1) +
(kVA L2) + (kVA L3).
8001
kVA Sys Net
System Net Apparent Power (kVA). Signed net value of (kVA L1) + (kVA L2)
+ (kVA L3).
8010
kVA L1
Individual Phase Apparent Powers (kVA) (Signed)
8020
kVA L2
"
8030
kVA L3
"
8040
kVA Dem System Max
System Maximum Instantaneous kVA Demand (kVA, resettable). It displays
the default value after a CAM until 1 demand window elapses. After a power
cycle or CPU reset, the value is not reset and does not update again until 1
demand window elapses. (Unsigned/Absolute)
8050
kVA Dem System Now
Average kVA for most recent demand window (resettable). Displays the
default value after a CAM or reset, or power cycle. Updates every minute
thereafter. True demand value takes a demand period to get to actual value.
(Unsigned/Absolute)
9000
DPF
System Total Displacement Power Factor (PF) (Signed)
9030
APF
System Total Apparent Power Factor (PF) (Signed)
9060
DPF L1
Individual Phase Displacement Power Factor (PF)
9090
DPF L2
"
9120
DPF L3
"
9150
APF L1
Individual Phase apparent Power Factors (PF)
9180
APF L2
"
9210
APF L3
"
10000
Frequency
Line Frequency (Hz)
10010
Time Since Reset
Seconds since accumulator registers were reset.
12000
CTA Phase Sh
All CT phase shift (degrees)
12001
CT1 Phase Sh
CT1 phase shift (degrees)
12002
CT2 Phase Sh
CT2 phase shift (degrees)
12003
CT3 Phase Sh
CT3 phase shift (degrees)
12010
CTA Value
All Value