Appendices
Appendix B - MD-BMS and MD-BMED Power Meters Modbus Absolute/Net Value Measurement Registers and
Protocol Commands
81
Building Technologies
125-202
06/06/2017
Modbus
Offset
Register
Description
contain that value; otherwise, it will be zero).
46015
6014
Positive Apparent PF System
System Positive Apparent Power Factor (aPF);
Register is 100x actual value (If the System aPF
(44015) is positive, this register will contain that
value; otherwise, it will be zero).
46016
6015
Amps System Avg
Average of the current in all phases.
46017
6016
Volts Line to Line Avg
Average of the system line to line voltages.
46018
6017
Volts Line to Neutral Avg
Average of the system line to neutral voltages.
46019
6018
Volts L1 to L2
Individual phase to phase voltages
46020
6019
Volts L2 to L3
“
46021
6020
Volts L3 to L1
“
46022
6021
Measured Line Frequency
Line frequency x 10 (e.g., 602 = 60.2 Hz). On
startup, 20 point averaging array is filled with first
frequency read.
46023
6022
Positive kWh L1 LSW
Individual Phase Positive True Energy LSW (kWh,
resettable)
46024
6023
Positive kWh L1 MSW
Individual Phase Positive True Energy MSW
(kWh, resettable)
46025
6024
Positive kWh L2 LSW
"
46026
6025
Positive kWh L2 MSW
"
46027
6026
Positive kWh L3 LSW
"
46028
6027
Positive kWh L3 MSW
"
46029
6028
Positive kW L1
Individual Phase Instantaneous Positive True
Powers (kW)
46030
6029
Positive kW L2
"
46031
6030
Positive kW L3
"
46032
6031
Positive kVARh L1 LSW
Individual Phase Positive Reactive Energy LSW
(kVARh, resettable)
46033
6032
Positive kVARh L1 MSW
Individual Phase Positive Reactive Energy MSW
(kVARh, resettable)
46034
6033
Positive kVARh L2 LSW
"
46035
6034
Positive kVARh L2 MSW
"
46036
6035
Positive kVARh L3 LSW
"
46037
6036
Positive kVARh L3 MSW
"
46038
6037
Positive kVAR L1
Individual Phase Positive Instantaneous Reactive
Powers (kVAR)