Installation
MD-BMS and MD-BMED Power Meters Wiring Diagrams
52
Building Technologies
125-202
06/06/2017
Typical 115V Single-Phase Panel Setup
Connect the Black L1 voltage lead to Voltage L1 (hot), Red L2 voltage lead to Neutral,
and White N voltage lead to Neutral. CT1 will monitor the L1 load. CT3 can be used if
the Blue L3 voltage lead is connected to L1. CT3 could then monitor any L1 branch
circuit.
System Values
System values are the sum of L1 + L2 + L3 measurements. System values may not be
meaningful since two different devices or loads can be monitored by a single MD-BMS
or MD-BMED element.
When paired with the correct voltage phase, each CT provides individual kW/kWh
readings for that CT channel.
MD-BMS and MD-BMED Power Meters Wiring Diagrams
The MD-BMS and MD-BMED Power Meters can be wired using any one of the
following five common wiring setups. These diagrams will assist you in properly
connecting your power meter for the setup desired.
NOTE:
All wire colors are U.S. Standard, and differ from Canadian standards.
For Canadian installations, reverse the red and black wires (L1 = Red, L2 = Black).
WARNING
DO NOT EXCEED 600 Vac PHASE-TO-PHASE CAT III.
When complete, close the enclosure cover, if equipped.
WARNING
Hazardous voltages exist.
MD-BMS and MD-BMED Power Meters should only be wired by qualified personnel.