Appendices
Appendix B - MD-BMS and MD-BMED Power Meters Modbus Absolute/Net Value Measurement Registers and
Protocol Commands
76
Building Technologies
125-202
06/06/2017
Modbus
Offset
Register
Description
44051
4050
Displacement PF L2
"
44052
4051
Displacement PF L3
"
44053
4052
Apparent PF L1
Individual Phase apparent Power Factors (PF)
44054
4053
Apparent PF L2
"
44055
4054
Apparent PF L3
"
44056
4055
Amps L1
Individual Phase Currents (A)
44057
4056
Amps L2
"
44058
4057
Amps L3
"
44059
4058
Volts L1 to Neutral
Individual Phase to Neutral Voltages (V)
44060
4059
Volts L2 to Neutral
"
44061
4060
Volts L3 to Neutral
"
44062
4061
Time Since Reset LSW
Seconds since KWH register was reset. LSW
44063
4062
Time Since Reset HSW
Seconds since KWH register was reset. MSW
44064
4063
Data Tick Counter
Internal sample count (gets cleared every minute): may
be used to determine if sample read is a newer sample
than last read.
44080
4079
kW System Average
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable).
44081
4080
kW Demand System Min
System Minimum Demand (kW)
44082
4081
kVA Demand System Max System Maximum Instantaneous kVA Demand (kVA,
resettable). It displays the default value after a CAM
until one demand window elapses. After a power cycle
or CPU reset, the value is not reset and does not
update again until one demand window elapses.
44083
4082
kVA Demand System Now System Average kVA Demand For the most recent
(current) Demand Window (resettable). Displays the
default value after a CAM or reset, or power cycle.
Updates every minute thereafter. True demand value
takes a demand period to get to actual value. Similar to
44005.
44084
4083
kVAR Demand System
Max
System Maximum kVAR Demand (kVAR, resettable). It
displays the default value after a CAM until one
demand window elapses. After a power cycle or CPU
reset, the value is not reset and does not update again
until one demand window elapses.