Appendices
Appendix B - MD-BMS and MD-BMED Power Meters Modbus Absolute/Net Value Measurement Registers and
Protocol Commands
82
Building Technologies
125-202
06/06/2017
Modbus
Offset
Register
Description
46039
6038
Positive kVAR L2
"
46040
6039
Positive kVAR L3
"
46041
6040
kVAh L1 LSW
Individual Phase Apparent Energy LSW (kVAh,
resettable)
46042
6041
kVAh L1 MSW
Individual Phase Apparent Energy MSW (kVAh,
resettable)
46043
6042
kVAh L2 LSW
“
46044
6043
kVAh L2 MSW
“
46045
6044
kVAh L3 LSW
“
46046
6045
kVAh L3 MSW
“
46047
6046
kVA L1
Individual Phase Instantaneous Apparent Powers
(kVA)
46048
6047
kVA L2
“
46049
6048
kVA L3
“
46050
6049
Positive Displacement PF L1
Individual Phase Positive Displacement Power
Factors (dPF); Register is 100 × actual value (If
the Individual dPF (44050) is positive, this register
will contain that value; otherwise, it will be zero).
46051
6050
Positive Displacement PF L2
"
46052
6051
Positive Displacement PF L3
"
46053
6052
Positive Apparent PF L1
Individual Phase Positive Apparent Power Factors
(aPF); Register is 100 × actual value (If the
Individual aPF(44053) is positive, this register will
contain that value; otherwise, it will be zero).
46054
6053
Positive Apparent PFL2
"
46055
6054
Positive Apparent PF L3
"
46056
6055
Amps L1
Individual Phase Instantaneous Currents (A)
46057
6056
Amps L2
“
46058
6057
Amps L3
“
46059
6058
Volts L1 to Neutral
Individual Instantaneous Phase to Neutral
Voltages (V)
46060
6059
Volts L2 to Neutral
“
46061
6060
Volts L3 to Neutral
“
46062
6061
Time Since Reset LSW (Seconds)
Seconds since kWh, kVAh, kVARh and
associated Demand registers were reset. LSW
(resettable).
46063
6062
Time Since Reset MSW (Seconds) Seconds since CAM. MSW