278/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
19 Addendum 4: LMV52... with O2 trim control and O2 module
13.08.2004
Terminal
marking
Connection
symbol
E
ing
an
g
A
us
gang
Description of connection
Electrical limit values
PIN 6
x
Temperature compensation QGO... (U3)
DC [0...2 V], Ri > 100 k
Ω
PIN 5
x
Power supply temperature compensation (G2)
DC [12...18 V], Ra = 20
Ω
PIN
4
x x GND
(M)
PIN 3
x
Thermocouple (B2)
DC [0...33 mV], Ri > 100 k
Ω
PIN
2
x x GND
(M)
X81
PIN 1
x
Nernst voltage (B1)
DC [-25...1 mV], Ri > 100 k
Ω
PIN 5 GND
x
Signal reference
PIN 4 CANL
x
Communication signal
PIN 3 CANH
x
Communication signal
DC U <= 5 V, Rw = 120
Ω
,
Level to ISO-DIS 11898
PIN 2 12VAC2
x
AC supply for O
2
module
X84
PIN 1 12VAC1
x
AC supply for O
2
module
AC12V +10%/-15%, 50...60 Hz,
Fuse max. 4 A
PIN 5 GND
x
Signal reference
PIN 4 CANL
x
Communication signal
PIN 3 CANH
x
Communication signal
DC U <= 5 V, Rw = 120
Ω
,
Level to ISO-DIS 11898
PIN 2 12VAC2
x
AC supply for O
2
module
X85
PIN 1 12VAC1
x
AC supply for O
2
module
AC12V +10%/-15%, 50...60 Hz,
Fuse max. 4 A
Combustion air / flue gas temperature sensor
PIN 3
x
Shield connection
PIN 2
x
Signal reference
X86
PIN 1
x
Flue gas temperature sensor input Pt1000 /
LG-Ni 1000
PIN 3
x
Shield connection
PIN 2
x
Signal reference
X87
PIN 1
x
Combustion air temperature input Pt1000 /
LG-Ni 1000
PIN 1 PE
x
Protective earth (PE)
PIN 2 Q5 N
x
QGO... heating N (Q5)
X89-02
PIN 3 Q4 L
x
QGO... heating L (Q4)
At AC 120 V +10 %/-15 %,
50...60 Hz, Imax. 2.5 A
At AC 230 V +10 %/-15 %,
50...60 Hz, Imax. 2.5 A
PIN 4 PE
x
Protective earth (PE)
PIN 5 N
x
Power supply neutral conductors (N)
X89-01
PIN 6 L
x
Power supply live conductor (L)
10%/-15%, 50...60Hz,
Imax. 2.5 A