235/301
Siemens Building Technologies
Basic Documentation LMV5...
CC1P7550en
HVAC Products
16 Addendum 1: List of fault status messages of LMV5... system
13.08.2004
Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5x system
Troubleshooting
A6
4E
LC
Internal Fault Load Controller
CAN error
*1)
A6
50
LC
Short-circuit Pt100 Sensor
Short-circuit sensor PT100 (X60.1 X60.4) Check wiring and sensor
A6
51
LC
Open-circuit Pt100 Sensor
Open-circuit sensor PT100 (X60.1 X60.4) Check wiring and sensor
A6
52
LC
Open-circuit Pt 100 Sensor (Line
Compens)
Open-circuit compensation line of sensor
PT100 (X60.2 X60.4)
Check wiring and sensor
A6 53 LC
Short-circuit
Pt1000
Sensor
Short-circuit sensor PT1000 (X60.3
X60.4)
Check wiring and sensor
A6
54
LC
Open-circuit PT1000 Sensor
Open-circuit sensor PT1000 (X60.3
X60.4)
Check wiring and sensor
A6 55 LC
Short-circuit
Ni1000
Sensor
Short-circuit sensor Ni1000 (X60.3 X60.4) Check wiring and sensor
A6
56
LC
Open-circuit Ni1000 Sensor
Open-circuit sensor Ni1000 (X60.3
X60.4)
Check wiring and sensor
A6
57
LC
Overvoltage at Input 2
Overvoltage at input 2 (X61)
Check wiring and sensor
A6
58
LC
Open-circuit / Short-circuit at In-
put 2
Open-circuit / short-circuit input 2 (X61)
Check wiring and sensor
A6
59
LC
Overvoltage at Input 3
Overvoltage at input 3 (X62)
Check wiring and sensor
A6
5A
LC
Open-circuit / Short-circuit at In-
put 3
Open-circuit / short-circuit input 3 (X62)
Check wiring and sensor
A6
60
LC
Internal Fault Load Controller
Timeout during calibrate_ADC
*1)
A6
61
LC
Internal Fault Load Controller
Timeout during read_conversion
*1)
A6
62
LC
Internal Fault Load Controller
Timeout during calibrate_ADC
*1)
A6
63
LC
Internal Fault Load Controller
Fault during RedInv reading from A/D
converter
*1)
A6
64
LC
Internal Fault Load Controller
Fault internal A/D converter
*1)
A6
65
LC
Internal Fault Load Controller
Gain register has been changed
*1)
A6
66
LC
Internal Fault Load Controller
Offset register has been changed
*1)
A6
67
LC
Internal Fault Load Controller
Too great / small gain for self-calibration
of A/D converter
*1)
A6
68
LC
Internal Fault Load Controller
Too great / small offset for self-calibration
of A/D converter
*1)